10 exam-style questions with answers and explanations, straight from our 1,030-question bank. Tap an answer to check yourself. When you're ready, take the scored version in the free practice test.
The Electrical Levels 1-4 exam has 103 questions and runs 3 hours.
These 10 free Electrical Levels 1-4 questions are organized by exam domain, so you can see how each part of the NCCER Electrical Levels 1-4 blueprint is tested. Reveal the answer and explanation under each question.
Domain 1: Wireways, Raceways, and Fittings 18% of exam
Question 1
An electrician has shut down a conveyor, opened and isolated its disconnect, applied a personal lock and tag, and bled off the stored energy in the drive's capacitors. What must be done before any work begins on the equipment?
Show answer & explanation
Correct answer: D - Verify the zero-energy state by testing the circuit
Question 2
A 4 in. square box contains six 12 AWG conductors that enter the box and are spliced inside, two 12 AWG equipment grounding conductors, two internal cable clamps, and one duplex receptacle mounted on a yoke. What is the total conductor count for the box fill calculation?
Show answer & explanation
Correct answer: B - 10 conductors
Question 3
An electrician must offset a run of 1/2 in. EMT to clear a 4 in. obstruction using two 30° bends. What is the distance between the two bend marks?
Show answer & explanation
Correct answer: C - 8 in.
Question 4
During an inspection, an electrician points to an Informational Note in the NEC to justify an installation method. How must that Informational Note be treated?
Show answer & explanation
Correct answer: A - As explanatory material that is not enforceable as a requirement
Domain 2: Residential Wiring 12% of exam
Question 5
A 200 A service is supplied by 3/0 AWG copper service-entrance conductors. What is the minimum size copper grounding electrode conductor required?
Show answer & explanation
Correct answer: C - 4 AWG
Question 6
A 480 V, three-phase load draws 40 A at a power factor of 0.85. What is the true power delivered to the load?
Show answer & explanation
Correct answer: B - 28.3 kW
Question 7
A three-phase motor is running under load when one line fuse opens. What is the most likely immediate result?
Show answer & explanation
Correct answer: A - The motor continues to run but draws excessive current on the remaining phases
Question 8
A sump pump motor is controlled by a float switch wired directly into the magnetic starter's coil circuit. After a brief power outage, the motor restarts by itself with no one present. Which statement best explains this?
Show answer & explanation
Correct answer: C - A two-wire control circuit provides no low-voltage protection
Question 9
The available fault current at a panelboard is calculated at 18,000 A. Which branch-circuit breaker may be installed in that panelboard?
Show answer & explanation
Correct answer: D - A breaker with a 22,000 A interrupting rating
Domain 3: Hand Bending 9% of exam
Question 10
Six current-carrying 8 AWG THWN-2 copper conductors are installed in a single raceway at an ambient temperature of 30°C. The circuit terminates on equipment rated 75°C. What ampacity may be used for these conductors?
Show answer & explanation
Correct answer: B - 44 A
The rest of the Electrical Levels 1-4 blueprint
The Electrical Levels 1-4 exam also covers these domains. Drill them in the full free practice test:
Domain 4: Safety For Electricians9% of exam
Domain 5: Outlet, Device, Pull, and Junction Boxes9% of exam
Domain 6: Conductors and Cables9% of exam
Domain 7: Introduction to Electrical Circuits7% of exam
Domain 8: Electrical Theory7% of exam
Domain 9: Introduction to the National Electrical Code7% of exam
Domain 10: Basic Electrical Construction Documents6% of exam
Domain 11: Electrical Test Equipment4% of exam
Domain 12: Occupational Overview: The Electrical Industry3% of exam
That's 10 of 1,030
The full bank has 1,020 more Electrical Levels 1-4 questions with explanations.