10 exam-style questions with answers and explanations, straight from our 1,030-question bank. Tap an answer to check yourself. When you're ready, take the scored version in the free practice test.

Start the free practice test → ★★★★★4.9/5 from 2,400+ candidates · No signup

The Electrical Levels 1-4 exam has 103 questions and runs 3 hours.

These 10 free Electrical Levels 1-4 questions are organized by exam domain, so you can see how each part of the NCCER Electrical Levels 1-4 blueprint is tested. Reveal the answer and explanation under each question.

Domain 1: Wireways, Raceways, and Fittings 18% of exam

Question 1

An electrician has shut down a conveyor, opened and isolated its disconnect, applied a personal lock and tag, and bled off the stored energy in the drive's capacitors. What must be done before any work begins on the equipment?

Show answer & explanation

Correct answer: D - Verify the zero-energy state by testing the circuit

Question 2

A 4 in. square box contains six 12 AWG conductors that enter the box and are spliced inside, two 12 AWG equipment grounding conductors, two internal cable clamps, and one duplex receptacle mounted on a yoke. What is the total conductor count for the box fill calculation?

Show answer & explanation

Correct answer: B - 10 conductors

Question 3

An electrician must offset a run of 1/2 in. EMT to clear a 4 in. obstruction using two 30° bends. What is the distance between the two bend marks?

Show answer & explanation

Correct answer: C - 8 in.

Question 4

During an inspection, an electrician points to an Informational Note in the NEC to justify an installation method. How must that Informational Note be treated?

Show answer & explanation

Correct answer: A - As explanatory material that is not enforceable as a requirement

Domain 2: Residential Wiring 12% of exam

Question 5

A 200 A service is supplied by 3/0 AWG copper service-entrance conductors. What is the minimum size copper grounding electrode conductor required?

Show answer & explanation

Correct answer: C - 4 AWG

Question 6

A 480 V, three-phase load draws 40 A at a power factor of 0.85. What is the true power delivered to the load?

Show answer & explanation

Correct answer: B - 28.3 kW

Question 7

A three-phase motor is running under load when one line fuse opens. What is the most likely immediate result?

Show answer & explanation

Correct answer: A - The motor continues to run but draws excessive current on the remaining phases

Question 8

A sump pump motor is controlled by a float switch wired directly into the magnetic starter's coil circuit. After a brief power outage, the motor restarts by itself with no one present. Which statement best explains this?

Show answer & explanation

Correct answer: C - A two-wire control circuit provides no low-voltage protection

Question 9

The available fault current at a panelboard is calculated at 18,000 A. Which branch-circuit breaker may be installed in that panelboard?

Show answer & explanation

Correct answer: D - A breaker with a 22,000 A interrupting rating

Domain 3: Hand Bending 9% of exam

Question 10

Six current-carrying 8 AWG THWN-2 copper conductors are installed in a single raceway at an ambient temperature of 30°C. The circuit terminates on equipment rated 75°C. What ampacity may be used for these conductors?

Show answer & explanation

Correct answer: B - 44 A